Model |
HYU-FA-IOM001-1 |
|
Power |
|
| Operating voltage |
DC (17~30) V |
| Start-up current |
≤ 1.5 mA |
| Input voltage (pulsed) |
DC (5~9) V |
|
Quiescent Condition |
|
| Quiescent condition input resistance |
(8k2 ~ 47k) Ω |
| Quiescent current with 22 kΩ EOL fitted |
≤ 700 μA |
| Sampling time |
1s |
| Polling indicator |
Flashing green |
|
Input Alarm |
|
| Alarm condition input resistance |
(2k2 ~ 8k2) Ω |
| Alarm current |
2mA |
| Alarm indicator |
Red |
|
Output |
|
| Output relay type |
SPDT. 2A@DC 30V / 0.5A@AC125V |
| Output relay wetting current |
10 μA @ DC 10 mV |
| Output relay active indicator |
Red |
| Output relay active current |
2mA |
|
Fault Condition |
|
| Input short-circuit Fault condition resistance |
≤ 2k2 Ω |
| Input open-circuit Fault condition resistance |
≥ 47k Ω |
|
Isolator |
|
| Switching current (max) |
1.0A |
| Switching resistance (max) |
0.3 Ω |
| Isolator indicator |
Yellow |
|
Environment |
|
| Operating temperature |
(-10 ~ +50) °C |
| Operating humidity |
(0 ~ 95) % RH, non-condensing |
| Storage temperature |
(-25 ~ +80) °C |
| Storage humidity |
(0 ~ 98) % RH, non-condensing |
|
Miscellaneous |
|
| Number of inputs |
1 |
| Number of outputs |
1 |
| Usable addresses per alarm loop |
125ST 250XP |
| Terminal wiring |
0.4 ~ 2.5mm² |
| Dimensions |
95x95x42mm |
| Ingress protection rating |
IP-54 |